The ETTROIT JX3416610 is a 16A four-pole (4P) residual current circuit breaker designed to protect three-phase systems with neutral. Its 30mA differential sensitivity ensures high safety against earth leakage and indirect contact, protecting people and equipment.
The F trip curve ensures rapid and selective tripping, ideal for electronic equipment and circuits with moderate inrush currents, with faster tripping times than traditional B and C curves.
Compliant with IEC/EN61008-1, the circuit breaker has a breaking capacity of 6kA and tripping times of ≤0.1s. It features a front test button for periodic checking of correct operation. It occupies 4 DIN modules on a 35mm rail, compatible with standard electrical panels.
- Pure differential protection against earth leakage
- Rated current: 16A
- Differential sensitivity: 30mA
- Intervention curve: F (fast and selective, suitable for electronics)
- Poles: 4P (three-phase + neutral)
- Breaking capacity: 6kA
- Rated voltage: 380V~ 50Hz
- IEC/EN61008-1 standard
- Front test button
- DIN rail installation
- Size: 4 DIN modules